Product Name: P5 Drive 600 Volt
Product Description
Specifications and Features: -
The GPD 506/P5 is designed specifically for applications where overload and starting torque requirements are well known. Common applications of this type include fans, centrifugal pumps, commercial laundry machines, grinders, buffers, low-viscosity mixers, centrifuges and saws.
Constant torque and variable torque ratings.
V/Hz Control Mode.
Alpha/numeric operator...Full function LCD english language operator and keypad with easy-to-read 16 character two-line format display. Easy input and monitoring of operating parameters.
Built-in PID control...Eliminates cost of external device. Full featured scalable PID feedback with display and an inverse signal function.
Energy savings control...Automatic output voltage adjustment in response to actual motor loading. Real-time energy savings based on motor algorithms. Increases motor efficiency by several percent.
Network Communications links to DeviceNet or ModBus RTU.
Under torque detection...Alerts the operator to conditions such as loss of load or broken fan belts.
Dual-bridge, 12-pulse rectification...By using a zig-zag input transformer with dual secondary, input current harmonic distortion factor can be reduced over 90%.
Peformance Features
Ratings:
2 to 200 HP (VT) at 600 VAC
Overload capacity:
VT 120% for 60 sec (180% peak)
CT 150% for 60 sec (200% peak)
Starting torque: 150%
DC injection braking: ramp or coast to stop, adjustable, current limited
Electronic reversing
Adjustable accel/decel: 0.1 to 3600 sec (2 each)
Controlled speed range: 40:1
Critical frequency rejection: 2 selectable, adjustable bands
Drive efficiency: 96 to 98%
Energy $aving control: improves motor efficiency
Displacement power factor: 0.98
Output frequency: 0.1 to 400 Hz
Frequency resolution:
0.01 Hz with digital reference,
0.06 Hz with analog reference
Frequency regulation:
0.01% digital (-10 ° to 40 °C),
0.1% analog (15 ° to 35 °C)
Torque boost: full range, auto
Jog forward and reverse
Power loss ride-thru: 2 sec
Inertia ride-thru
Selectable auto restart after momentary power loss
Programmable auto restart (0 to 10 attempts) after resettable fault
Slip Compensation
Protective Features
Current limited stall prevention
Synchronized start into rotating motor via speed search
DC bus CHARGE indicator
Optically-Isolated controls
Phase-to-phase / phase-to-neutral short circuit protection
Ground fault protection
Electronic motor overload
Current and torque limit
Fault circuit: overcurrent, overvoltage, and overtemperature
Over torque protection
Under torque protection
Design Features
32-bit microprocessor logic
Surface mount devices
Carrier frequency: selectable to 15 kHz
Keypad operator controls
LCD display: English alpha/numeric sixteen character two lines
24 VDC control logic
Programmable contacts, one form C and one NO
Timer function: contact-initiated
RS-232 communications port
Volts/hertz ratio: Programmable custom V/Hz patterns
Multi-speed settings: 6 available
Remote speed reference:
0 to 10 VDC or 4 to 20 mA
Setpoint (PID) control with inverse input and Sleep function
Signal follower: bias and gain
Analog monitor output: 0 to 10 VDC
NEMA 1 enclosed or protected chassis
UL, cUL and ce listed; IEC 146
MTBF: exceeds 28 years
Service Conditions
Ambient service temperature:
-10°C to 40°C (104°F) NEMA 1, to 45°C (113°F) protected chassis
Humidity: non-condensing to 95%
Altitude: to 3300 ft; higher by derating
Input voltage: +10%/-15%, 500 to 600 VAC
Input frequency: 50/60 Hz ± 5%
3-phase, 3-wire, phase sequence insensitive
| Related Products: |
"HIGH PERFORMANCE GAS DRIVE" K-18, "HIGH PERFORMANCE GAS DRIVE" K-18 G, "HIGH PERFORMANCE GAS DRIVE" K-30G, "HIGH PERFORMANCE GAS DRIVE" K-50 G, "HIGH PERFORMANCE GAS DRIVE" K-70, "THE QUIET MACHINE" K-50, "The Ultimate Performance Rotary Screw Air Compressor" HERCULES 15, 20, 25, 30 & 40 Horsepower Models, "The Ultimate Performance Rotary Screw Air Compressor" HERCULES 40, 50 & 60 Horsepower Models, .965in Male - 1.25in Female Adapter, 1 GPM Electrocoagulation System, 1-amp battery charge controller supports universal Li-ion designs, 1-amp buck regulator can be programmed to one of four output voltages, 1-amp buck regulator can be programmed to one of four output voltages, 1-amp buck regulator can be programmed to one of four output voltages, 1.25in Dropin Extension Tube with 1in Eye Piece Push Back, 1.25in Male - 2in Female Adapter, 1.25in Threadin Extension Tube with 1in Eye Piece Push Back, 1.5-Ton pipe roll, 100SB Series PathfinderTM Heavy Duty Rotating Light, 102 Series Triliptical Stackable Status Indicator, 11) KNIGHT AIR ROLL HANDLING SYSTEM, 12" bench top positioner Welding Positioners, 12-Ton pipe roll, 12-Ton vessel roll vessel turning rolls, 12mm Inline Geared Motors (Square / Double Ended Type) |
|
|
|
|